S10 Power system analysis · Practice
Midterm exam
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A 60 MW load at 0.9 power factor lagging is served at 138 kV.
(a)
Line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Capacitor to reach 0.98?
Check
A machine (40 MVA, 22 kV, X = 0.1 pu) and a 230 kV line of j40 Ω, on 100 MVA with 24 kV on the machine's side.
(a)
Machine's X?
(b)
Line's X?
(c)
Current on the line for a bolted fault at its far end (1 pu source)?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A short-circuit test reads 400 V, 4 A, 600 W; and a transformer with R = 0.015, X = 0.06 pu at full load, 0.8 lagging.
(a)
Leakage reactance from the test?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Regulation of the second transformer?
Check
Phases spaced 6, 7, 18 m; two-conductor bundles 0.4 m apart; conductor GMR 13 mm, radius 13 mm.
(a)
L per km?
Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.
(b)
C per km?
Check
A 500 kV line with L = 0.9 mH/km and C = 10 nF/km, 500 km long.
(a)
SIL?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Open-end voltage rise?
Check
Buses at 0.98 and 0.96 pu, 28° apart, across X = 0.35 pu.
(a)
Real power?
(b)
Reactive power leaving bus 1?
Check
A 1 pu source feeds a unity-pf load of 0.4 pu through X = 0.2 pu.
(a)
Load voltage?
(b)
Maximum deliverable?
Check
A line of X = 0.35 pu with 0.3 series compensation; a 120 Mvar capacitor at 0.92 pu.
(a)
Transfer limit between 1 pu buses?
(b)
Capacitor output?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Generator j\given0.15 at bus 1; bus 3 fed directly by j\given0.1 and via bus 2 by j\given0.15 + j\given0.35; the j\given0.1 line has total charging 0.1 pu.
(a)
?
(b)
Net susceptance the j\given0.1 line adds to bus 3's diagonal?
Check
A 118-bus case with 12 PV buses; and a two-bus case with X = 0.25 and a 1 pu load.
(a)
Unknowns in the first?
(b)
Angle after Newton's first step in the second?
Check
Two-bus: X = 0.15, load 0.5 + j0.4, flat start.
(a)
First Gauss–Seidel iterate's magnitude?
(b)
Converged magnitude?
Check
A triangle with = 0.1, = 0.15, = 0.35 pu carrying 250 MW from bus 1 to bus 3.
(a)
Flow on line 1–3?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Angle drop across line 1–2 (100 MVA base)?
Check
A stiff 1 pu source closes, through a resistance of 200 Ω, onto an unloaded lossless line 300 km long with = 300 Ω and wave speed 295 km/ms.
(a)
Size of the first wave launched, in per unit?
(b)
When does it reach the far end?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(c)
Far-end voltage just after it arrives, in per unit?
(d)
Far-end voltage after the second arrival, at three travel times, in per unit?
Check
Line ℓ carries 0.5 pu and line k carries 0.7 pu. Line k carries 0.75 of any transfer between its own ends, and line ℓ carries 0.35 of it. A generator's shift factor on line ℓ is −0.3 with line k in service (100 MVA base).
(a)
Line ℓ's outage distribution factor for line k?
(b)
Line ℓ's flow after line k trips?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(c)
Line ℓ is rated 80 MW. Ignoring the outage's effect on the shift factor, how much must that generator raise its output beforehand to keep line ℓ within its rating after the outage?
Check
A conductor of 22 mm with 0.07 Ω/km at 75 °C sits in 25 °C air with h = 25 W/m²K, ε = α = 0.5 and 1000 W/m² of sun.
(a)
What is its 75 °C ampacity?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 1 pu source feeds 0.9 pu at power factor 0.9 lagging through X = 0.2 pu.
(a)
What is the loadability margin?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10