S10 Power system analysis · Practice
Problem set 10: power systems across the course
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A 345 kV line, 150 km: phases spaced 7, 8, 20 m; two-conductor bundles 0.4 m apart, conductor GMR 14 mm.
(a)
Total series reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Transfer limit between buses held at rated voltage?
Check
A generator (X″ = 0.15) and transformer (X = 0.1, 100 MVA) feed a 230 kV line of j80 Ω, faulted at its far end; the line's relay uses a 100:5 CT and very inverse curve, dial 1, pickup 0.5 × 5 A.
(a)
Fault current on the line?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Multiple of pickup?
(c)
Relay time?
Check
A slack at 1∠0° serves 0.6 + j0.5 pu through X = 0.15.
(a)
Load voltage?
(b)
Capacitor (pu) to bring the load to 0.95 lagging?
Check
A generator ( = 1) delivers 0.7 + j0.5 at 1 pu; in a transient stability study its is 2.2 pu.
(a)
Internal voltage |E|?
(b)
Critical clearing angle for a zero-transfer fault?
Check
Two units (5, 0.003) and (6.5, 0.008) share 300 MW; unit 1's loss sensitivity is 0.03.
(a)
λ ignoring losses, dollars per MWh?
(b)
Unit 1's effective incremental cost at that dispatch?
Check
A 40 GW system (synchronous H = 3 s, 0.6 inverter-based, droop 0.04, D = 1) loses 3 GW.
(a)
Initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
(b)
Settling frequency deviation?
Check
A 138 kV bus (100 MVA base) with = j0.15, = j0.1.
(a)
Line-to-ground fault current?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
(b)
Line-to-line fault current?
Check
A triangle ( = 0.1, = 0.15, = 0.35 pu) carries 250 MW from bus 1 to bus 3; line 1–3 is rated 120 MW.
(a)
Flow on line 1–3?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
Largest transfer before line 1–3 overloads?
Check
Two machines (H = 3 and 5 s) with E = 1.15 pu each, joined by X = 0.8 pu, 15° apart.
(a)
Synchronizing coefficient?
(b)
Swing frequency?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A 12.47 kV feeder 4 km long (z = 0.2 + j0.45 Ω/km) with 5 MW of evenly spread unity-pf load; a 1 Mvar capacitor at a 60 MVA bus.
(a)
Voltage drop at the end?
(b)
Capacitor's resonant harmonic?
Check
A line of 30 Ω (CT ratio 200, VT ratio 3000), with L = 1.2 mH/km and C = 10 nF/km over 200 km.
(a)
Zone 1 setting at 80%, secondary ohms?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Open-end Ferranti rise?
Check
A 118-bus case with 12 PV buses; and a two-bus case with X = 0.2, load 1.2 + j0.2.
(a)
Jacobian size?
(b)
Angle after Newton's first step?
(c)
Voltage after Newton's first step?
Check
A 1 pu source feeds a load at power factor 0.85 lagging through X = 0.25 pu.
(a)
What is the most it can deliver?
(b)
At what voltage?
Check
A generator rated 1 pu ( = 1.1, field limit 2 pu) runs at 0.85 pu and 1 pu.
(a)
What vars does its armature limit allow?
(b)
And its field limit?
Check
Two 100 MW units with outage rates 0.04 and 0.05 serve a 150 MW load.
(a)
What is the loss-of-load probability?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10