S10 Power system analysis · Practice
Problem set 12: operating the grid
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
An area's tie-line flow is 50 MW from schedule, frequency is −0.04 Hz from 60, and its bias is −400 MW/0.1 Hz.
(a)
What is its area control error?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
An interconnection of 50 GW (all generation at droop 0.04, load damping D = 1.5) loses 2.5 GW.
(a)
Where does its frequency settle, relative to 60 Hz?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
(b)
What is its frequency response, in MW per 0.1 Hz (negative)?
Check
A 40 GW system's synchronous units have H = 4 s, and 0.6 of its generation is inverter-based without inertia. It loses 3 GW.
(a)
What is the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
Two meters on one flow read 0.95 pu (σ = 0.01) and 1.12 pu (σ = 0.05).
(a)
What is the WLS estimate?
(b)
What is the normalized difference between the readings (above 3 suggests bad data)?
Check
A monitored line carries 0.4 pu; line k carries 0.6 pu. For a transfer between line k's ends, line k itself takes 0.6 and the monitored line 0.35.
(a)
What is the outage distribution factor?
(b)
What does the monitored line carry if line k trips?
Check
A line's PTDF for a 100 MW transaction is 0.25; it already carries 500 MW against a 600 MW rating.
(a)
What will it carry with the transaction?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
What's the largest such transaction its rating allows?
Check
A line rated 800 A at static conditions sheds 45 W/m by convection, 15 W/m by radiation and absorbs 14 W/m of sun. Measured wind raises convection 2.5 times.
(a)
What is its dynamic rating?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 2 pu transfer splits between path A (x = 0.05 pu, rated 1 pu) and path B (x = 0.15 pu). A phase shifter on A may be used.
(a)
What does A carry naturally?
(b)
What phase shift (negative relieves A) brings A to its rating, if it's over?
Check
A remote generator priced 20 dollars per MWh sends 400 MW with losses (B = 0.0001 per MW) to a bus where congestion adds 15 dollars per MWh.
(a)
What is the receiving bus's LMP?
Check
A utility serving 20000 customers had 15000 customer interruptions in a year, averaging 120 minutes each.
(a)
What is its SAIFI?
(b)
What is its SAIDI?
Check
Inverters export 4 MW and absorb 1.5 Mvar at the end of a 12.47 kV feeder of 1 + j2 Ω.
(a)
How much do they change the voltage there?
(b)
How many vars would cancel the rise completely?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
Each phase of a balanced four-wire load draws 50 A of fundamental, 10 A of third harmonic and 15 A of fifth.
(a)
What is each phase's current THD?
(b)
What flows in the neutral?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A rectifier's valve-side line voltage is 200 kV RMS; it fires at α = 10° and carries 3 kA through a commutating reactance of 15 Ω.
(a)
What is its DC voltage?
Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.
(b)
What power does it deliver?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S10